Error
Error definition and causes
code
D255H
The target station number of the dedicated
instruction is incorrect.
D256H
The execution or error completion type of
the dedicated instruction is incorrect.
D257H
The request type of the REQ instruction is
incorrect.
D258H
The control station does not exist when the
dedicated instruction was executed to the
specified control station or current control
station.
D25AH
The dedicated instruction was executed
specifying the channel in use.
D25BH
The dedicated instruction was executed
specifying the channel in use.
D25DH
The transient data is incorrect.
D25FH
The REMFR/REMTO/REMFRD/REMTOD/
REMFRIP/REMFRDIP/REMTOIP/
REMTODIP instruction was executed from
a module with a station type that cannot
execute it.
D260H
The REMFR/REMTO/REMFRD/REMTOD/
REMFRIP/REMFRDIP/REMTOIP/
REMTODIP instruction was executed from
a module with a station type that cannot
execute it.
D262H
The total number of slave stations
specified in the CCPASET/CCPASETR
instruction is incorrect.
D263H
The constant link scan time setting of the
CCPASET/CCPASETR instruction is
incorrect.
D264H
The station number setting of the
CCPASET/CCPASETR instruction is
incorrect.
D265H
The station number specified for the
CCPASET/CCPASETR instruction is
already in use.
D266H
The number of occupied stations specified
in the CCPASET/CCPASETR instruction is
incorrect.
D267H
The station type of the CCPASET/
CCPASETR instruction is incorrect.
19 LIST OF ERROR CODES
424
19.1 Error Codes When a Module Error Occurs
Action
• Execute the instruction again after correcting the target station number in
the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the execution or error
completion type in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the request type in the
request data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the target station number in
the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Retry the operation after a while.
• Change the channels used by own station or the target station storage
channel in the control data.
Change the channels used by own station or the target station storage
channel in the control data.
• Execute the instruction again after correcting the transient data at the
transient request source.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
The REMFR/REMTO/REMFRD/REMTOD/REMFRIP/REMFRDIP/
REMTOIP/REMTODIP instruction can only be used for a master station.
Modify the program so the REMFR/REMTO/REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP instructions are not used.
The REMFR/REMTO/REMFRD/REMTOD/REMFRIP/REMFRDIP/
REMTOIP/REMTODIP instruction can only be used for a master station.
Modify the program so the REMFR/REMTO/REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP instructions are not used.
• Execute the instruction again after correcting the total number of slave
stations in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the constant link scan time
in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station number in the
network configuration setting data so it is within 1 to 120.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station number in the
network configuration setting data to a unique value.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the number of occupied
stations in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
• Execute the instruction again after correcting the station type in the
network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.