Error Codes For The Message Communication Function (Client) - Mitsubishi Electric MELSEC iQ-R Series User Manual

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

19.4
Error Codes for the Message Communication
Function (Client)
Error codes for the message communication function (client) are stored in the following.
• 'Result storage area' (Un\G7752706) of the Class3/UCMM communication area (response area) (for the 1st code)
• o_uStatusId of each module function block (error code when a communication error)
Error code
Error definition and causes
0001H
A value outside the range was set
for the request area or the input
argument of the module function
block.
0002H
The size of the received data
exceeded 1414 bytes.
0003H
The connection set for the Class3
reserved station was used.
0004H
Class3 communications were
performed using an area where
Class3 communications
parameters were not set.
0005H
UCMM communications were
performed using an area where
Class3 communications
parameters were set.
0006H
Class3 communications failed.
0101H
A request for UCMM/Class3
communications failed to be sent.
0102H
There was no response to a
request for UCMM/Class3
communications.
0103H
Connection establishment for
Class3 communications failed.
0104H
There was no response to
ForwardOpen for performing
Class3 communications.
0165H
The number of simultaneous
executions for UCMM
communications has reached its
upper limit.
01FFH
An error was set to the CIP
response code.
Action
• Check the value set for the request area.
• Check the value set for the argument of the module function block.
• Check the settings of the external device.
• Check that there is no noise on the line.
Check the Class3 communication parameters and change the connection destination from the
reserved station.
• Check that the area used is correct.
• Set Class3 communications parameters in the area used.
Perform UCMM communications using an area where Class3 communication parameters are not set.
• Check that the Ethernet cable is not disconnected.
• Check by using PING or a similar method that a module with the request source IP address exists
on the network.
• Check that the Ethernet cable is not disconnected.
• Check by using PING or a similar method that a module with the request source IP address exists
on the network.
• When UCMM communications are requested, check that the external device supports UCMM
communications.
• When Class3 communications are requested, check that the external device supports Class3
communications.
• Check that there is no noise on the line.
• Check by using PING or a similar method that a module with the request source IP address exists
on the network.
• When UCMM communications are requested, check that the external device supports the UCMM
communication server function.
• When Class3 communications are requested, check that the external device supports the Class3
communication server function.
• Refer to the manual for the external device and check that the external device is ready to receive a
request.
• Check that there is no noise on the line.
• Check that the request destination IP address set in the Class3 communications parameters is
correct.
• Check that the external device supports the Class3 communication server function.
• Check that there is no noise on the line.
• Check that the external device supports the Class3 communication server function.
• Refer to the manual for the external device and check that the external device is ready to receive a
request.
• Check that there is no noise on the line.
• Reduce the number of UCMM communication connections executed simultaneously.
• Execute again at a later time.
Refer to the manuals for the external device and the EtherNet/IP specification (THE CIP NETWORKS
LIBRARY Volume 1 Common Industrial Protocol (CIP
notification is made for this error and the action to take.

19.4 Error Codes for the Message Communication Function (Client)

*1
*2
)) to check the conditions under which a
19 LIST OF ERROR CODES
19
441

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents