■Structure of Mixture of CC-Link IE TSN Class B/A
No.1
Class B (1Gbps)
Basic cycle
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
No.0: Master station (CC-Link IE TSN Plus module)
No.1 and No.2: Local station (device where the network synchronous communication setting is set to "Synchronous")
No.3: Remote station (device where the network synchronous communication setting is set to "Synchronous")
No.4: Remote station (device where the network synchronous communication setting is set to "Asynchronous")
No.5, No.6, and No.7: Remote station
(1) Ethernet device (1Gbps)
(2) Ethernet device (100Mbps)
Synchronization is possible using network synchronous communication.
Even for a CC-Link IE TSN Class B device, synchronization is not possible if the network synchronous communication setting is set to "Asynchronous".
For a CC-Link IE TSN Class A device, synchronization is not possible using network synchronous communication.
No.2
No.3
Class B (1Gbps)
Class B (1Gbps)
Basic cycle
Basic cycle
9.7 CC-Link IE TSN Network Synchronous Communication Function
No.4
General-
Class B (1Gbps)
purpose hub
Basic cycle
No.5
Class A (100Mbps)
9 FUNCTIONS
(1)
9
(2)
205