Mitsubishi Electric MELSEC iQ-R Series User Manual page 527

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Master station  remote station
When data is sent from the master station (RY/RWw) to a remote station (output).
Calculation value
Normal value
Maximum value
■Variable
Name of variable
SM
LS
Rio
n2
Master station  local station
When data is sent from a local station to the master station as follows:
• Master station (RX)  local station (RY)
• Master station (RWr)  local station (RWw)
• Master station (LB)  local station (LB)
• Master station (LW)  local station (LW)
Calculation value
Station-based block data assurance
If LS < SL: (SM  1) + (LS  (n1 + 1)) + (SL  1)
Normal value
If LS  SL: (SM  1) + (LS  (n1 + 2))
(SM  2) + (LS  (n1 + 2)) + (SL  1)
Maximum value
■Variable
Name of variable
Description
SM
Master station sequence scan time
LS
Communication cycle intervals (can be checked in the
SW0060)
SL
Local station sequence scan time
Round up the calculated value to the nearest integer of (SM 
n1
LS)
Master station  local station
When data is sent from the master station to a local station as follows:
• Master station (RY)  local station (RX)
• Master station (RWw)  local station (RWr)
• Master station (LB)  local station (LB)
• Master station (LW)  local station (LW)
Calculation value
Station-based block data assurance
If LS < SM: (SM  1) + (LS  (n3 + 1)) + (SL  1)
Normal value
If LS  SM: (LS  (n3 + 2)) + (SL  1)
(SM  1) + (LS  (n3 + 2)) + (SL  2)
Maximum value
■Variable
Name of variable
Description
SM
Master station sequence scan time
LS
Communication cycle intervals (can be checked in the
SW0060)
SL
Local station sequence scan time
Round up the calculated value to the nearest integer of (SL 
n3
LS)
Station-based block data assurance
(SM  n2) + (LS  1) + Rio
(SM  n2) + (LS  2) + Rio
Description
Master station sequence scan time
Communication cycle intervals (can be checked in the SW0060)
Processing time of the remote station
Round up the calculated value to the nearest integer of (LS  SM)
No station-based block data assurance
(SM  1) + (LS  1) + Rio
(SM  2) + (LS  2) + Rio
Unit
s
s
s
No station-based block data assurance
(SM  1) + (LS  2) + (SL  1)
(SM  2) + (LS  3) + (SL  1)
Unit
s
s
s
No station-based block data assurance
(SM  1) + (LS  2) + (SL  1)
(SM  1) + (LS  3) + (SL  2)
Unit
s
s
s
Appendix 6 CC-Link IE TSN Processing Time