Mitsubishi Electric MELSEC iQ-R Series User Manual page 132

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Setting the Class1 instance communications
To perform Class1 instance communications for the EtherNet/IP device, follow the procedure below.
1.
Connect the engineering tool to the originator side and register the EDS file of the target side from the "EtherNet/IP
Configuration" window. ( Page 129 Adding the EDS file)
2.
Select the EtherNet/IP device of the target side in "Module List" and drag it to the list of EtherNet/IP devices.
3.
Set the items such as the device name and IP address of the EtherNet/IP device of the target side.
4.
Double-click "<Detailed Setting>" in the "Connection Setting" column and set the connection of the EtherNet/IP device.
(The setting window that opens from "<Detailed Setting>" of each line is the same.)
5.
Configure the settings to send data to the adapter using the own station (originator) as a scanner.
Select the EtherNet/IP device under "Scanner" in "Connection List" and click the [Add Connection] button.
6.
Select "Input Only (Class1 Instance)" in "Select Connection to be Added:" and click the [OK] button.
7.
Set the parameter for the Class1 instance communications in "Detailed Connection Settings". ( Page 122
Connections: Scanner (Input Only (Class1 Instance)))
• For "Instance ID" under "Input T->O", set the instance ID of the connection you wish to communicate with as
the target.
• For "Data Size" under "Input T->O", set the data size of the connection you wish to communicate with as the
target.
8 PARAMETER SETTINGS
130
8.2 EtherNet/IP Parameter Settings

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-r cc-link ie tsn plus

Table of Contents