Mitsubishi Electric MELSEC iQ-R Series User Manual page 127

Master/local module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Item
Timeout Multiplier
Input T->O
Input Mode
Real Time Format
Data Size
Priority
RPI
Output O->T
Output Mode
Real Time Format
Priority
RPI
Check
Compatible Mode
Identity
Vendor Code Check
Product Type Check
Product Code Check
Major Revision Check
Minor Revision Check
*1 Some values cannot be set depending on the EDS file of the communication destination.
Description
Set the timeout multiplier.
Set the transmission mode for packets containing input data.
The setting items depend on the EtherNet/IP device to be used.
• Multicast: Multicast (one to many) communications are performed.
• Point to point: Unicast (one to one) communications are performed.
Displays the realtime format.
Set the data size to be sent from the target to the originator.
(Unit: Bytes)
Set the priority of the connection.
The setting items depend on the EtherNet/IP device to be used.
Set the request packet interval (RPI). (Unit: 500s)
Set the transmission mode for packets containing output data.
The setting items depend on the EtherNet/IP device to be used.
• Multicast: Multicast (one to many) communications are performed.
• Point to point: Unicast (one to one) communications are performed.
This is fixed to "Point to point" if the adapter is a CC-Link IE TSN Plus
module.
Displays the realtime format.
Set the priority of the connection.
The setting items depend on the EtherNet/IP device to be used.
Set the request packet interval (RPI). (Unit: 500s)
Enables or disables compatible mode.
For details, refer to the following.
Page 265 Consistency check
Set whether or not to check the vendor code.
Set whether or not to check the product type.
Set whether or not to check the product code.
Set whether or not to check the major revision.
Set whether or not to check the minor revision.
*1
Setting range
• 4
• 8
• 16
• 32
• 64
• 128
• 256
• 512
(Default: 4)
• Multicast
• Point to point
(Default: Multicast)
1 to 1444
(Default: 2)
• Low
• High
• Scheduled
• Urgent
(Default: Scheduled)
500 to 60000000
(Default: 20000)
• Multicast
• Point to point
(Default: Multicast)
• Low
• High
• Scheduled
• Urgent
(Default: Scheduled)
500 to 60000000
(Default: 20000)
• Disabled
• Enabled
(Default: Disabled)
• Disabled
• Enabled
(Default: Disabled)
• Disabled
• Enabled
(Default: Disabled)
• Disabled
• Enabled
(Default: Disabled)
• Disabled
• Enabled
(Default: Disabled)
• Disabled
• Enabled
(Default: Disabled)
8 PARAMETER SETTINGS
8.2 EtherNet/IP Parameter Settings
8
125