2.
Click the [OK] button to finish the interlink transmission settings.
Item
Description
Transfer Source Module
Select the combination of transfer source and transfer destination modules.
Transfer Destination
Module
Setting method
Right-click in the "Interlink Transmission Parameters" window and select a link device setting method
from the "Setting Method" menu.
• Start/End: Enter the start and end numbers of link devices.
• Points/Start: Enter the numbers of points and start numbers of link devices.
RX/LB
Source
Enter the link device range of the transfer source and destination modules. Up to 64 interlink
LB/RY
transmission ranges can be set. RX and RY points can be assigned in increments of 16 (Start: 0H,
Destination
End: FH).
RX
RX
RX
RWr/LW
Source
Enter the link device range of the transfer source and destination modules. Up to 64 interlink
LW/RWw
transmission ranges can be set. RWr and RWw points can be assigned in increments of 4.
Destination
RWr
RWr
RWr
Link devices set for "Source" can be overlapped. Doing so will allow transfer of the same link devices to
multiple network modules.
No.1
LB
No.2
LB
No.64
LB
No.1
LW
No.2
LW
No.64
LW
No.1
LB
RY
No.2
RY
LB
No.64
RY
LB
No.1
LW
RWw
No.2
RWw
LW
No.64
RWw
LW
8.1 Parameter Settings for CC-Link IE TSN
Setting range
The setting varies
depending on the set
module.
• Start/End
• Points/Start
(Default: Start/End)
RX: 0H to 3FFFH
RY: 0H to 3FFFH
(Default: empty)
RWr: 0H to 1FFFH
RWw: 0H to 1FFFH
(Default: empty)