7.
Set the network configuration as follows. (Set the IP address for each station.)
[Navigation window] [Parameter] [Module Information] [RJ71GN11-EIP(T+E)] [Port1 Module Parameter (CC-
Link IE TSN)] [Basic Settings] [Network Configuration Settings] [Detailed Setting]
In this manual, "Authentication Class" is described as "CC-Link IE TSN Class".
8.
Click the [Close with Reflecting the Setting] button to close the "CC-Link IE TSN Configuration" window.
9.
Set the refresh settings as follows.
[Navigation window] [Parameter] [Module Information] [RJ71GN11-EIP(T+E)] [Port1 Module Parameter (CC-
Link IE TSN)] [Basic Settings] [Refresh Settings] [Detailed Settings]
10.
In "Communication Mode" under "Application Settings", set "Unicast" or "Multicast".
[Navigation window] [Parameter] [Module Information] [RJ71GN11-EIP(T+E)] [Port1 Module Parameter (CC-
Link IE TSN)] [Application Settings] [Communication Mode]
11.
Click the [Apply] button.
12.
Write the set parameters to the CPU module on the master station. Then, reset the CPU module or power off and on the
system.
[Online] [Write to PLC]
In this example, default values are used for parameters that are not shown above. For the parameters, refer to
the following.
Page 73 Parameter Settings for CC-Link IE TSN
11.2 Communication Example of the Master Station and Local Stations
11 PROGRAMMING
221
11