Instantiating Psm_Ref In Automation Studio; Instantiating Dam_Ref In Automation Studio; Instantiating Acm_Ref In Automation Studio - Danfoss VLT ISD 510 Operating Manual

Servo drive system
Hide thumbs Also See for VLT ISD 510:
Table of Contents

Advertisement

VLT® Servo Drive System ISD 510/DSD 510
Operating Guide
1.
Create 1 instance of function block AXIS_REF_DDS (located in folder DDS_Drive) for every servo drive that has to be control-
led or monitored.
2.
To create a link to the physical servo drive, link each instance of AXIS_REF_DDS to 1 physical servo drive. This makes it the
logical representation of 1 physical servo drive.
-
Open the Logical View.
-
Initialize each instance with its node number and the slot name it is connected to (for example, IF3).
-
Initialize each instance of a drive with its DriveType.
Example
Illustration 57: Instantiation of AXIS_REF_DDS and Setting of Initial Values

6.10.6 Instantiating PSM_REF in Automation Studio™

Procedure
1.
Create 1 instance of function block PSM_REF (located in folder DDS_PSM) for every Power Supply Module (PSM) that has to
be controlled or monitored.
2.
To create a link to the physical PSM, link each instance of PSM_REF to 1 physical PSM. This makes it the logical representa-
tion of 1 physical PSM.
-
Open the Logical View.
-
Initialize each instance with its node number and the slot name it is connected to (for example, IF3).

6.10.7 Instantiating DAM_REF in Automation Studio™

Procedure
1.
Create 1 instance of function block DAM_REF (located in folder DDS_DAM) for every Decentral Access Module (DAM) that
has to be controlled or monitored.
2.
To create a link to the physical DAM, link each instance of DAM_REF to 1 physical DAM. This makes it the logical representa-
tion of 1 physical DAM.
-
Open the Logical View.
-
Initialize each instance with its node number and the slot name it is connected to (for example, IF3).

6.10.8 Instantiating ACM_REF in Automation Studio™

Procedure
1.
Create 1 instance of function block ACM_REF (located in folder DDS_ACM) for every Auxiliary Capacitors Module (ACM) that
has to be controlled or monitored.
2.
To create a link to the physical ACM, link each instance of ACM_REF to 1 physical ACM. This makes it the logical representa-
tion of 1 physical ACM.
-
Open the Logical View.