Pins
Description
5
GND
6
VCC
-
Only PELV potential can be connected to the LCP input.
11.9.7 AC Mains Connector
The AC mains connector is located on the bottom of the Power Supply Module (PSM 510).
Illustration 147: AC Mains Connector
Table 141: Pin Assignment of AC Mains Connector
Descrip-
Notes
Pins
tion
(left to
right)
1
L3
Used to connect
L1/L2/L3
2
L2
3
L1
11.9.7.1 Mains Cable Cross-Sections for PSM 510
Table 142: Mains Cable Cross-Sections for PSM 510
Minimum cable cross-section for CE
Minimum cable cross-section for UL
11.9.8 Relay Connector
The relay connector is used for a user-defined reaction and is located as follows:
Power Supply Module PSM 510: 1 relay connector
Auxiliary Capacitors Module ACM 510: 1 relay connector
-
Only PELV potential can be connected to the relay outputs.
Danfoss A/S © 2020.08
Notes
GND
5 V supply for LCP
N O T I C E
Rating/parameter
Nominal voltage: 400–480 V AC ±10%
Nominal power: 30 kW
Maximum cross-section: 16 mm
Conductor cross-section range 0.75–16 mm
PSM 510 (10 kW)
2
4 mm
(minimum 70 °C, Cu)
AWG 10
(minimum 60 °C, Cu)
N O T I C E
Rating/parameter
5 V ±10% at 120 mA maximum load
2
(AWG 4)
2
, solid or flexible (AWG 18–AWG 4)
PSM 510 (20 kW)
2
16 mm
(minimum 70 °C, Cu)
AWG 6
(minimum 60 °C, Cu)
AQ262449648484en-000101 / 175R1135 | 207
Specifications
PSM 510 (30 kW)
2
16 mm
(minimum 90 °C, Cu)
AWG 4
(minimum 75 °C, Cu)