Page 73
Check for loose or missing wiring. 2049 Power data restarted. It may be necessary to contact Danfoss Service or the 2064–2072 H081x: Option in slot x has restarted. supplier. Note the code number for further troubleshooting 2080–2088 H082x: Option in slot x has issued a power-up directions.
Page 74
Check parameter 5-00 Digital I/O ALARM 50, AMA calibration failed Mode and parameter 5-01 Terminal 27 Mode. Contact the Danfoss supplier or Danfoss Service. WARNING 41, Overload of digital output terminal 29 ALARM 51, AMA check U...
Page 75
The control card and power card are incompatible. To WARNING 62, Output frequency at maximum limit check compatibility, contact the Danfoss supplier with the The output frequency is higher than the value set in type code of the unit from the nameplate and the part parameter 4-19 Max Output Frequency.
Page 82
5–8 rectifier. Voltage and parameter 300-22 CT Nominal Voltage are set ALARM 250, New spare part correctly. If so, contact Danfoss or supplier. The power or switch mode supply has been exchanged. ALARM 312, CT range Restore the filter type code in the EEPROM. Select the Current transformer measurement limitation was detected.
1500 2000 2500 3000 Altitude (meters above sea level)* Illustration 8.10 Altitude Derating Non-UL compliance If UL/cUL is not to be complied with, Danfoss recommends using the following fuses, which ensure compliance with EN50178: N132-N200 380-500 V type gG P250-P400...
Page 120
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.