Delta ASDA-A3 Series User Manual page 312

Hide thumbs Also See for ASDA-A3 Series:
Table of Contents

Advertisement

ASDA-A3
Z: positive / negative direction selection of linear scale feedback
0: positive direction when A phase leads B phase of linear scale
1: positive direction when B phase leads A phase of linear scale
U: linear scale filter function
0: bypass
1: 6.66 M
2: 1.66 M
3: 833 K
4: 416 K
5 – F: reserved
P1.075
Default:
100
Unit:
ms
Format:
DEC
Settings:
When the stiffness of the mechanical system between full- and half-closed loops is insufficient, set the
proper time constant to enhance the stability of the system. In other words, temporarily create the
half-closed loop effect, and after stabilizing, the full-closed loop effect is created. When the stiffness is
sufficient, set to bypass.
Set the value to 0 to disable the low-pass filter (bypass) function.
If the stiffness of the mechanical system is high, decrease the value of P1.075, or set the value to 0 to
disable. If the stiffness of the mechanical system is low, increase the value of P1.075.
P1.076▲
Default:
5500
Unit:
rpm
Format:
DEC
Settings:
Input the actual maximum speed of the motor as the reference value to activate the smoothing function.
When you set the value to 0, the smoothing function is disabled.
P1.077 –
P1.080
Revision December, 2017
Low-pass filter time constant for full- and half-closed loop
control
Maximum speed for encoder output (OA, OB)
Reserved
Control mode: PT
Setting range: 0 – 1000
Data size:
16-bit
Control mode: All
Setting range: 0 – 6000
Data size:
16-bit
Parameters
Address: 0196H
0197H
Address: 0198H
0199H
8-55
8