Parameters
P1.004
Default:
8
Unit:
Format:
Settings:
Please refer to P0.003 for the analog output setting.
Example 1:
If the requirement is for the motor to run at 1000 rpm, which corresponds to 8V, and its maximum speed
is 5000 rpm, the setting is:
P1.004 =
Refer to the following example for the motor's current speed and relative voltage output:
Motor speed
300 rpm
900 rpm
P1.005
Default:
Unit:
Format:
Settings:
Please refer to P0.004 for the analog output setting.
P1.006
Default:
Unit:
Format:
Settings:
0: disable this function
P1.007
Default:
Unit:
Format:
Settings:
0: disable this function
8-34
MON1 analog monitor output proportion
100
% (full scale)
DEC
×100% =
Required speed
1000 rpm
Maximum speed
5000 rpm
MON1 = 8V ×
Current speed
Maximum speed×
MON1 = 8V ×
Current speed
Maximum speed×
MON2 analog monitor output proportion
100
% (full scale)
DEC
Speed command smoothing constant (Low-pass filter)
0
ms
DEC
Torque command smoothing constant (Low-pass filter)
0
ms
DEC
Control mode: All
Setting range: 0 – 100
Data size:
16-bit
×100% = 20%
MON1 analog monitor output
×100% =8V ×
300 rpm
P1.004
5000 rpm×
20
100
100
×100% =8V ×
900 rpm
20
P1.004
5000 rpm×
100
100
Control mode: All
Setting range: 0 – 100
Data size:
16-bit
Control mode: S / Sz
Setting range: 0 – 1000
Data size:
16-bit
Control mode: T / Tz
Setting range: 0 – 1000
Data size:
16-bit
Address: 0108H
0109H
×100% = 2.4V
×100% = 7.2V
Address: 010AH
010BH
Address: 010CH
010DH
Address: 010EH
010FH
Revision December, 2017
ASDA-A3