Parameter
Offset
Step 8 Click Connection Test to start the connection test.
Step 9 After the connection test is successful, click
information.
----End

6.4.2.2.4 Viewing a Temperature Map on the NetEco

Prerequisites
Procedure
Step 1 Choose Monitor > Topo > Data Center View from the main menu, and click the
management domain for which a temperature sensor has been deployed in the navigation tree
on the left.
Step 2 Click
Issue 03 (2019-03-10)
Description
The offset value varies with the ports on the independent deployment
AI/DI unit.
The following figure shows the ports on the independent deployment
AI/DI unit. If the NTC sensor is connected to port AI/DI_1, the offset
is 0. If the NTC sensor is connected to port AI/DI_2, the offset is 1,
and so on.
A temperature sensor has been successfully connected.
You have logged in to the NetEco client.
You have created a management domain for the device to be added on the Data Center
Planning page.
to view the temperature map.
Copyright © Huawei Technologies Co., Ltd.
in the toolbar to save the device
6 Adding Devices