iManager NetEco 6000
Device Installation and Commissioning Guide
Connecting Cables to the Double Door Interlock
Issue 03 (2019-03-10)
Figure 4-37 Connecting cables to the single-door magnetic lock and emergency door release
button
The double door interlock applies only to the four-door access controller.
Magnetic lock 1 is installed on door 1, and magnetic lock 2 is installed on door 2.
Card readers 1 and 2 are bound to the inside and outside of door 1. Card readers 3 and 4
are bound to the inside and outside of door 2.
The CH2 and CH4 terminals on the right can be connected to the door status sensor. If
the door status sensor is not connected, short-circuit the ST and GND terminals.