7.1.2.2 Routine Maintenance for Temperature Sensors

Table 7-9 Routine Maintenance for Temperature Sensors
Item
Check the
availability of
the temperature
sensor.

7.1.2.3 Routine Maintenance for the Temperature and Humidity Sensor

Table 7-10 Routine maintenance for the temperature and humidity sensor
Item
Check the
availability of
the temperature
and humidity
sensor.

7.1.2.4 Routine maintenance for the camera

Table 7-11 Routine maintenance for the camera
Item
Issue 03 (2019-03-10)
Maintenan
ce Interval
Semi-annua
lly
Maintenan
ce
Frequency
Semi-annua
lly
Mai
Method
nten
ance
Inte
rval
Copyright © Huawei Technologies Co., Ltd.
Method
Expected
Result
Hold the
Hold the
temperature
temperature
sensor probe in
sensor probe in
your palm, and
your palm, and
check the
check the
temperature
temperature
displayed for the
displayed for the
corresponding
corresponding
rack
rack environment
environment unit
unit on the
on the WebUI.
WebUI.
Method
Expected
Result
Check the
The reading is
reading on the
normal and
temperature and
accurate.
humidity sensor.
Expected
Result
7 Device Maintenance
Exception
Handling
If the
temperature does
not go up, check
whether the
temperature
sensor cable is
loose or
disconnected. If
so, reconnect the
cable. If not,
replace the
temperature
sensor.
Troubleshooti
ng
If the reading is
inaccurate, check
and calibrate the
temperature and
humidity sensor
using a
temperature and
humidity
measuring
instrument with
higher precision.
Exception Handling