Step 7 Click Connection Test to start the connection test.
Step 8 After the connection test is successful, click
information.
----End

6.4.5 Adding a UPS

6.4.5.1 Setting Monitoring Parameters for a UPS2000

Prerequisites
Context
Before connecting the UPS2000 to the NetEco, set monitoring parameters on the UPS2000.
Then, modify the port parameters for the collector connecting to the UPS2000 to ensure that
the values of BaudRate, DataBit, StopBit, and Parity on the UPS2000 are consistent with
those for the collector port.
Procedure
Step 1 Set the UPS2000 device address using the DIP switch S2 on the optional Modbus card.
Toggles 1 to 8 of DIP switch S2 specify the device address in binary mode. ON indicates 0,
and OFF indicates 1.
Table 6-40 Mapping between device addresses and Modbus card DIP switch settings
Device
Addre
ss
1
2
3
4
Step 2 Set RS485 port parameters for the collector based on the values of BaudRate, DataBit,
StopBit, and Parity of the device. For ECC collector settings, see
Parameters for the ECC500 V6
Issue 03 (2019-03-10)
You have obtained the IP address and user name and password for logging in to the
collector.
A PC with an IP address in the same network segment as the collector has been prepared
and connected to the collector over a switch.
Table 6-40
Toggle
Toggle
Switch
Switch
1
2
OFF
ON
ON
OFF
OFF
OFF
ON
ON
For the UPS2000, the default values of BaudRate, DataBit, StopBit, and Parity are 9600, 8, 1, and
None, respectively. If the parameters are changed, the actual parameter values prevail.
Copyright © Huawei Technologies Co., Ltd.
in the toolbar to save the device
shows an example of the address settings.
Toggle
Toggle
Toggle
Switch
Switch
Switch
3
4
5
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
Collector.
6 Adding Devices
Toggle
Toggle
Toggle
Switch
Switch
Switch
6
7
8
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
6.4.1.4 Setting RS485
233

Advertisement

Table of Contents
loading

Table of Contents