Connecting A Monitoring Cable To The Infrared Sensor - Huawei iManager NetEco 6000 Device Installation And Commissioning Manual

Hide thumbs Also See for iManager NetEco 6000:
Table of Contents

Advertisement

iManager NetEco 6000
Device Installation and Commissioning Guide
Table 4-10 Connecting cables to the smoke sensor
Core Wires of the Network Cable
Core wire 1 (orange-white), core wire 8
(brown)
Core wire 3 (green-white)
Core wire 6 (green)
Core wire 7 (brown-white)
None (reserved, cable connection not
required, only insulation required)
Step 4 Connect one end of the RJ45 network cable to the AI/DI port on the ECC500 collector.
----End

4.3.4.4 Connecting a Monitoring Cable to the Infrared Sensor

Prerequisites
A monitoring cable required is prepared.
Context
When connecting the infrared sensor and the ECC500 collector, you need to perform the
following steps to prepare a special monitoring cable.
Procedure
Step 1 Prepare an RJ45 connector on one end of the network cable by following to the instruction in
4.3.1 Preparing a Monitoring
Step 2 Connect the core wires of the network cable to the terminals for the infrared sensor, based on
the mappings in
Table 4-11 Connecting cables to the infrared sensor
Core Wires of the Network Cable
Core wire 3 (green-white)
Core wire 8 (brown)
Core wire 6 (green)
Core wire 7 (brown-white)
None (reserved, cable connection not
required, only insulation required)
Issue 03 (2019-03-10)
Cable.
Table
4-11.
Copyright © Huawei Technologies Co., Ltd.
4 Connecting Monitoring Cables to Devices
Cables for the Smoke Sensor
GND (black)
+12 V (red)
Normally closed end (yellow)
Common end (green)
Normally opened end (blue)
Infrared sensor terminals
+12V
GND
ALARM
ALARM
TAMPER
88