Step 2 When Add is displayed, set the device address by pressing + and -. When creating an ambient
temperature and humidity sensor on the NetEco, set Device address to the same value.
Step 3 Press Set.
Step 4 When bAu is displayed, retain the default value or change the baud rate by pressing + and -.
Set BaudRate for the collector port to the same value.
Step 5 Set RS485 port parameters for the collector based on the value of BaudRate, DataBit,
StopBit, and Parity of the device. For ECC collector settings, see
Parameters for the ECC500 V6
----End

6.4.2.3.2 Creating a Temperature and Humidity Sensor on the NetEco

Prerequisites
Procedure
Step 1 Choose Configuration > Configuration Management > Data Center Planning from the
main menu. The Data Center Planning window is displayed.
Step 2 Select the management domain to add a device.
Step 3 In the lower-left corner of the page, click the Device tab.
Step 4 Click the drop-down list box in Type and select Sensor.
Step 5 Select the device to be added and drag its icon to the management domain.
Step 6 Specify parameters shown in
T/H sensor complying with the MODBUS-RTU protocol is used as an example.
Issue 03 (2019-03-10)
Baud rates 12, 24, 48, and 96 on the temperature and humidity sensor panel represent 1200, 2400,
4800, and 9600, respectively.
DataBit, StopBit, and Parity for the ambient temperature and humidity sensor cannot be set on the
WebUI. Their values are 8, 1, and None respectively.
You have logged in to the NetEco client.
You have the operation rights for Data Center Planning.
You have created a management domain for the device to be added on the Data Center
Planning page.
To delete a device, click the device and choose Delete under
Copyright © Huawei Technologies Co., Ltd.
Collector.
Figure 6-73
in the right pane based on the following table. The
6 Adding Devices
6.4.1.4 Setting RS485
.
215

Advertisement

Table of Contents
loading

Table of Contents