Step 2 Connect the other end of the conversion cable to the water detector.
Figure 3-22 Connecting the water detector
Step 3 Plan the installation position for the fastener of the water detection cable. Ensure that the
water detection cable placed on the fastener is in good contact with the floor.
Do not contact the water detection cable to metal, for this action will cause a false alarm. Take
protective measures when routing a water detection cable.
Step 4 Tear off the protection paper on the rear of the fastener, then securely attach the fastener to
the floor.
Figure 3-23 Installing a fastener
Issue 03 (2019-03-10)
One fastener is provided for a 1 m long water detection cable.
When securing the water detection cable to the concrete floor, use the cable nail clips delivered with
the cable to secure the cable.