Step 7 Click Connection Test to start the connection test.
Step 8 After the connection test is successful, click
information.
----End

6.4.7 Adding a RPDU

6.4.7.1 Setting Monitoring Parameters for HPXPDU2000-16-3PH-24-6-M1

Prerequisites
Context
Before connecting the PDU2000 to the NetEco, set its device address and then modify the
port parameters for the collector connecting to the PDU2000 to ensure that the values of
BaudRate, DataBit, StopBit, and Parity on it are consistent with those for the collector port.
Procedure
Step 1 Press MENU on the PDU2000 display panel.
Step 2 Press UP until
Step 3 Press MENU,
Step 4 Press UP or DOWN to select the device address value.
Step 5 Press MENU to confirm the setting.
Step 6 Press Button.
Step 7 Set RS485 port parameters for the collector based on the values of BaudRate, DataBit,
StopBit, and Parity of the device. For ECC settings, see
for the ECC500 V6
Issue 03 (2019-03-10)
You have obtained the device address planned for the PDU2000.
The PDU2000 is connected to the collector, and digits are displayed on the LCD.
You have obtained the collector IP address and login user name and password.
A PC with an IP address in the same network segment as the collector has been prepared
and connected to the collector over a switch.
is displayed and ADD blinks.
is displayed, and 01 blinks. The current device address is 01.
If
is displayed, the setting succeeds.
If
is displayed, the setting fails. Reset the parameter.
The PDU2000 BaudRate, DataBit, StopBit, and Parity cannot be set on the WebUI. Their values are
9600, 8, 1, and None respectively.
is displayed. Then press MENU to exit.
Collector.