4.3.5 Connecting the Access Management System Cable

4.3.5.1 Connecting a Monitoring Cable to the A8802RS or A8804RS Access
Controller
General Cable Connections to an Access Controller
Figure 4-32 General cable connections for the access control system
Issue 03 (2019-03-10)
When connecting the door access system, you need to connect a door access controller,
an ECC500 collector, a door exit button, the fingerprint and card reader (with a keypad),
card reader with a keypad, single-door/double-door magnetic lock, and emergency door
release button.
Compared with the double-door access controller, the four-door access controller has one
more set of CH1 and CH2 terminals on the left and on the right respectively. The wiring
method remains unchanged.
You can connect the fingerprint and card reader (with a keypad), card reader with a
keypad, and exit button to the CH1 or CH2 terminal on the left of the access controller in
the following figure, and connect the double-door and single-door magnetic locks to the
CH1 or CH2 terminal on the right of the access controller in the following figure.
The following figure uses the double-door access controller as an example to illustrate
the wiring method for the access control system. In this example, the fingerprint and card
reader (with a keypad) connects to the CH1 terminal on the left of the access controller,
the card reader with a keypad connects to the CH2 terminal on the left of the access
controller, the double-door magnetic lock connects to the CH1 terminal on the right of
the access controller, and the single-door magnetic lock connects to the CH2 terminal on
the right of the access controller.
Connect the RS485 ports on the access controller and the fingerprint and card reader (with a keypad)
respectively to any two of COM1 to COM3 ports on the ECC500 collector.
Fingerprint and card reader (with a keypad) refers to the fingerprint and card reader with a keypad or
the fingerprint and card reader.
Copyright © Huawei Technologies Co., Ltd.