Step 4 Change the UPS2000-G SNMP trap parameters.
1.
2.
3.
4.
Issue 03 (2019-03-10)
Log in to the WebUI of the ECC500 V6 collector.
Choose System Settings > SNMP Settings.
In the SNMP Trap area, select the line where the value of Trap Target Address is the
same as the NetEco IP address before change, and click Delete.
Set Trap Target Address and Trap Port and select SNMP Version. Set Trap Target
Address to the NetEco server IP address and set Trap Port to the user-defined port. The
default value of Trap Port is 162.
Select SNMPv3 for SNMP Version and a user name for SNMPv3.
After you set the parameters, click Confirm and then click Submit.
Figure 8-8 Setting SNMPv3 parameters
Log in to the UPS2000-G WebUI.
Click Configure.
In the SNMP Trap area, select the line where the value of NMS addr is the same as the
NetEco IP address before change in the No. column, and click Delete.
Enter the NetEco server IP address in NMS addr, set Permission to Write, write 162 in
Trap port, and click Add.
Figure 8-9 Setting SNMP parameters_01
Copyright © Huawei Technologies Co., Ltd.
8 FAQ
304