Device Installation and Commissioning Guide

4.3.4 Connecting Sensors Cable

4.3.4.1 Connecting the Temperature Sensor Monitoring Cable

Prerequisites
A network cable used for monitoring is prepared.
Procedure
Step 1 Connect one end of the network cable to the wiring port on the temperature sensor.
Step 2 Connect the other end of the network cable to the AI/DI port on the AI/DI independent
deployment module.
----End

4.3.4.2 Connecting a Monitoring Cable to a Hydrogen Sensor

Prerequisites
The RS485 monitoring cable is prepared.
Procedure
Step 1 Connect one end of a common network cable to the hydrogen sensor RJ45 RS485 port.
Step 2 Connect the other end to the COM port on an ECC collector.
----End
4.3.4.3 Connecting a Monitoring Cable to the SDLH-94R Dry Contact-Type
Smoke Sensor
Prerequisites
A monitoring cable required is prepared.
Context
When connecting the SDLH-94R dry contact type smoke sensor and the ECC500 collector,
you need to perform the following steps to prepare a special monitoring cable.
Procedure
Step 1 Prepare an RJ45 connector on one end of the network cable by following to the instruction in
4.3.1 Preparing a Monitoring
Step 2 Short-circuit core wires 1 and 8 on the other end of the network cable.
Step 3 Connect the core wires of the network cable to the cables for the smoke sensor, based on the
mappings in
Issue 03 (2019-03-10)
Cable.
Table
4-10.
Copyright © Huawei Technologies Co., Ltd.
4 Connecting Monitoring Cables to Devices
87