Step 5 Check whether AI/DI_1 Sensor Type can be automatically identified. For example, Smoke
Sensor is automatically identified, as shown in
Figure 6-56 Setting the sensor type of a dry contact
Step 6 Set AI/DI_1 Power Supply to On.
Step 7 Click Submit.
----End

6.4.2.1.3 Setting Device Monitoring Parameters of an NO/NC Dry Contact on the ECC

After a normally open (NO) or normally closed (NC) dry contact is connected to the AI/DI
port of an ECC500 V6 collector, you need to set device parameters of the NO or NC dry
contact on the WebUI.
Prerequisites
Context
Procedure
Step 1 Log in to the WebUI of the ECC500 V6 collector.
Issue 03 (2019-03-10)
You have obtained the IP address, and login user name and password for the ECC500 V6
collector.
A PC with an IP address in the same network segment as the ECC500 V6 collector is
prepared, and the PC has been connected to the ECC500 V6 collector over a switch.
An NO or NC dry contact is a device whose normal status signal is open (or closed) and
whose alarm signal is closed (or open), such as a skylight controller.
This section describes how to set skylight controller monitoring parameters when a
skylight controller is connected to the AI/DI_1 port of the MUE05A4 card of an ECC500
V6 collector. Set the parameters based on the actual port connected to the skylight
controller onsite.