Figure 7-1 Direction of heat dissipation
7.1.2 Temperature and Humidity Requirements
To ensure continued safe and reliable equipment operation, install or position the
system in a well-ventilated, climate-controlled environment.
●
●
Table 7-1 Temperature and humidity requirements in the equipment room
Item
Temperature
Humidity
7.1.3 Cabinet Requirements
●
●
Issue 13 (2020-06-05)
Use temperature control devices all year long in any climates.
In dry and humid areas, maintain ambient humidity within range with
humidifiers and dehumidifiers respectively.
A general 19-inch cabinet with a depth of more than 1000 mm (39.37 in.)
which complies with the International Electrotechnical Commission 297 (IEC
297) standard.
Air filters installed on cabinet doors.
Copyright © Huawei Technologies Co., Ltd.
Description
5ºC to 35ºC (41ºF to 95ºF)
8% RH to 90% RH (non-condensing)
7 Installation and Configuration