Creating A Smart Cooling Product On The Neteco - Huawei iManager NetEco 6000 Device Installation And Commissioning Manual

Hide thumbs Also See for iManager NetEco 6000:
Table of Contents

Advertisement

iManager NetEco 6000
Device Installation and Commissioning Guide
Table 6-38 Parameter description
Parameter
Communication address
Baud Rate
The NetCol5000 DataBit, StopBit, and Parity cannot be set on the WebUI. Their default
values are 8, 1, and None respectively.
Step 5 Set RS485 port parameters for the collector based on the value of BaudRate, DataBit,
StopBit, and Parity of the device. For ECC collector settings, see
Parameters for the ECC500 V6
----End

6.4.4.2 Creating a Smart Cooling Product on the NetEco

Prerequisites
Procedure
Step 1 Choose Configuration > Configuration Management > Data Center Planning from the
main menu. The Data Center Planning window is displayed.
Step 2 Select the management domain to add a device.
Step 3 In the lower-left corner of the page, click the Device tab.
Step 4 Click the drop-down list box in Type and select Air Conditioner.
Step 5 Select the device to be added and drag its icon to the management domain.
Step 6 Specify parameters shown in
NetCol5000 smart cooling product complying with the MODBUS-RTU protocol is used as an
example.
Issue 03 (2019-03-10)
You have logged in to the NetEco client.
You have the operation rights for Data Center Planning.
You have created a management domain for the device to be added on the Data Center
Planning page.
To delete a device, click the device and choose Delete under
Copyright © Huawei Technologies Co., Ltd.
Description
1–255
Indicates the actual address for the
NetCol5000. The devices with the same
address cannot connect to the same port.
When creating a NetCol5000 on the
NetEco, set Device address to the same
value.
9600, 19200
Indicates the baud rate. The default baud
rate is 9600. Set BaudRate for the collector
port to the same value.
Collector.
Figure 6-80
in the right pane based on the following table. The
6 Adding Devices
6.4.1.4 Setting RS485
.
231