Function of the RS485 port on the ECC500 V6: When you create an RS485 device on the
NetEco, you need to enter the port number for connecting to the device on the NetEco.
The RS485 communications card can be inserted into any one or more slots among slots 1-4
on the ECC500 V6 collector. The RS485 port numbers vary based on slots.
the ECC500 V6 collector slots.
numbers.
During onsite operations, connect the slots on the collector based on site requirements. The
following figure is only for reference.
Figure 6-51 ECC500 V6 collector slots
(1) Slot 1
(3) Slot 3
Table 6-22 Mappings between port numbers and slot numbers
Slot
number
1
2
3
4
----End
Issue 03 (2019-03-10)
Only the device connected to the RS485 communciation card requires a port number. The devices
connected to the AI/DI card and independent deployment AI/DI unit do not require a port number.
COM1 port
number
3211
3216
3221
3226
Copyright © Huawei Technologies Co., Ltd.
Table 6-22
shows the mappings between slots and port
(2) Slot 2
(4) Slot 4
COM2 port
COM3 port
number
number
3212
3213
3217
3218
3222
3223
3227
3228
6 Adding Devices
Figure 6-51
COM4/12
COM5/12
V port
V port
number
number
3214
3215
3219
3220
3224
3225
3229
3230
shows
189