Huawei iManager NetEco 6000 Device Installation And Commissioning Manual page 109

Hide thumbs Also See for iManager NetEco 6000:
Table of Contents

Advertisement

iManager NetEco 6000
Device Installation and Commissioning Guide
Table 4-19 Indicator light definition
Terminal Identity
P
RUN
LK(1-4)
Table 4-20 RS485 interface
Terminal Identity
AL3(A8802RS)/AL5(A8
804RS)
Gnd
Table 4-21 Access control system cable list
BOM
Number
25030384
25030641
25030393
14180327
25031053
14180327
Issue 03 (2019-03-10)
Definition
The controller power light, red
Controller working indicator light, white blue, flashing
Lock status indicator light
Definition
RS485-A
RS485-B
BOM Description
Electric Cable, 300V/500V, 60227 IEC
2
53(RVV), 3x1mm
, Black(3Cores: Brown,
Blue, Yellow/Green), 10A, Outdoor Cable,
CCC, CE
Electric Cable, 300V, UL2464, 4x20AWG,
Black(4Cores: Yellow, Green, Violet,
White), 9A, Non-shielding Outdoor Cable,
UL
Electric Cable, 300V/500V, 60227 IEC
2
53(RVV), 2x0.75mm
, Black(2Cores:
Brown, Blue), 6A, Flat Outdoor Cable,
CCC, CE
Terminal Block, 4-Pin, Screw Fixed, 24–12
AWG, Pitch 5.08 mm, Male and Female
Using Together, Only for Power Supply
Electric Cable, 300V, UL2464, 7x20AWG,
Black(7Cores: Red, Black, Yellow, Green,
Orange, White, Blue), 9A, Non-shielding
Cable, UL
Terminal Block, 4-Pin, Screw Fixed, 24–12
AWG, Pitch 5.08 mm, Male and Female
Using Together, Only for Power Supply
Copyright © Huawei Technologies Co., Ltd.
4 Connecting Monitoring Cables to Devices
Cable Position
Access controller power cable
Cable from the magnetic lock
to the access controller
Cable from the emergency
door release button to the
access controller
Cable from the card reader to
the access controller
98

Advertisement

Table of Contents
loading

Table of Contents