7.1 Routine Maintenance

7.1.1 Monthly maintenance

7.1.1.1 Routine Maintenance for the Collector

Routine maintenance for the ECC500 collector is used as an example here. For the routine
maintenance for ECC800 collector, refer to section Routine Maintenance in ECC800 Data
Center Controller User Manual.
Table 7-1 Routine maintenance for the collector
Item
Main
control
module
Issue 03 (2019-03-10)
7
Mainte
Method
nance
Frequen
cy
Monthly
Check
whether the
indicators on
the main
control
module are
normal.
Copyright © Huawei Technologies Co., Ltd.

Device Maintenance

Expected
Symptom
Result
and
Possible
Cause
The RUN
The RUN
indicator
indicator is
blinks at long
off, indicating
intervals (on
that the main
for 1s and
control
then off for
module is in
1s).
poor contact
with the
The ALM
ECC500, is
indicator is
faulty, or has
off.
no power
input.
7 Device Maintenance
Exception
Handling
Check that
the main
control
module is in
good contact
with the
ECC500, runs
properly, and
has normal
power input.
249