Parameters: 15-** Drive Information - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions

3.15 Parameters: 15-** Drive Information

3.15.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
[0 - 2147483647 h] View how many hours the frequency
*
converter has run. The value is saved
when the frequency converter is
turned off.
15-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor has run.
*
2147483647 h]
Reset the counter in
parameter 15-07 Reset Running Hours
Counter. The value is saved when the
frequency converter is turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
[0 -
Register the power consumption of
*
2147483647
the motor as an average value over 1
kWh]
hour. Reset the counter in
parameter 15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 - 2147483647 ] View the number of times the frequency
*
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
temperature faults.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
overvoltages.
15-06 Reset kWh Counter
Option:
Function:
[0]
Do not reset
No reset of the kWh counter is required.
*
[1]
Reset counter Press [OK] to reset the kWh counter to 0
(see parameter 15-02 kWh Counter).
15-07 Reset Running Hours Counter
Option:
Function:
[0]
Do not
*
reset
[1]
Reset
To reset the running hours counter to 0, select
counter
[1] Reset and press [OK] (see
parameter 15-01 Running Hours). This
MG33MO02
Programming Guide
15-07 Reset Running Hours Counter
Option:
3.15.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (parameter 15-10 Logging Source) at individual rates
(parameter 15-11 Logging Interval). A trigger event
(parameter 15-12 Trigger Event) and window
(parameter 15-14 Samples Before Trigger) are used to start
and stop the logging conditionally.
15-10 Logging Source
Option:
[0]
*
[1472] VLT Alarm Word
[1473] VLT Warning Word
[1474] VLT Ext. Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor Current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1622] Torque [%]
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1650] External Reference
[1651] Pulse Reference
[1652] Feedback [Unit]
[1660] Digital Input
[1662] Analog Input 53
[1664] Analog Input 54
[1665] Analog Output 42 [mA]
[1666] Digital Output [bin]
[1675] Analog In X30/11
[1676] Analog In X30/12
[1677] Analog Out X30/8 [mA]
Danfoss A/S © 01/2018 All rights reserved.
Function:
parameter cannot be selected via the serial
port, RS485.
Select [0] Do not reset if no reset of the
running-hours counter is required.
Function:
Select which variables are to be
logged.
None
3
3
177

Hide quick links: