Danfoss VLT AutomationDrive FC 301 Programming Manual page 284

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Troubleshooting
Bit Hex
15 00008000
16 00010000
17 00020000
18 00040000
19 00080000
6
6
20 00100000
21 00200000
22 00400000
23 00800000
24 01000000
25 02000000
26 04000000
27 08000000 134217728 Brake IGBT (A27)
28 10000000 268435456 Option change
29 20000000 536870912 Drive initialized
30 40000000 1073741824 Safe stop (A68)
31 80000000 2147483648 Mech. brake low
Table 6.3 Description of Alarm Word, Warning Word, and Extended Status Word
The alarm words, warning words and extended status
words can be read out via a serial bus or optional fieldbus
for diagnostics. See also parameter 16-94 Ext. Status Word.
WARNING 1, 10 Volts low
The control card voltage is less than 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Maximum 15 mA or minimum 590 Ω.
A short circuit in a connected potentiometer or incorrect
wiring of the potentiometer can cause this condition.
282
VLT
Dec
Alarm word
32768
AMA not OK
65536
Live zero error (A2) Reserved
131072
Internal fault (A38) KTY error
262144
Brake overload
(A26)
524288
U phase loss (A30) ECB error
1048576
V phase loss (A31) Hoist
2097152
W phase Loss
(A32)
4194304
Fieldbus fault
(A34)
8388608
24 V supply low
(A47)
16777216
Mains failure (A36) Reserved
33554432
1.8 V supply low
(A48)
67108864
Brake resistor (A25) Motor rotating
(A67)
(A80)
(A63)
Danfoss A/S © 01/2018 All rights reserved.
®
AutomationDrive FC 301/302
Alarm word 2
Warning word
Reserved
No motor (W3)
Live zero error
(W2)
10 V low (W1)
Fans error
Brake overload
(W26)
Brake resistor
(W25)
Brake IGBT (W27)
mechanical
brake (A22)
Reserved
Speed limit (W49)
Reserved
Fieldbus fault
(W34)
Reserved
24 V supply Low
(W47)
Mains failure
(W36)
Current limit
Current limit (W59) Power Limit
(A59)
Low temp (W66)
unexpectedly
(A122)
Reserved
Voltage limit
(W64)
Reserved
Encoder loss (W90) Reserved
Encoder loss
Output freq. lim.
(A90)
(W62)
PTC thermistor
Safe stop (W68)
(A74)
Dangerous
Extended status
failure (A72)
word
Troubleshooting
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed in
parameter 6-01 Live Zero Timeout Function. The signal on 1
of the analog inputs is less than 50% of the minimum
Warning
Extended
word 2
status word
Auto DC
OVC active
braking
AC brake
KTY warn
Password timelock
number of allowed password trials
exceeded - timelock active
Fans warn
Password protection
0-61 = ALL_NO_ACCESS OR
BUS_NO_ACCESS OR
BUS_READONLY
ECB warn
Reference high
reference >parameter 4-55 Warning
Reference High
Hoist
Reference low
mechanical
reference <parameter 4-54 Warning
brake (W22)
Reference Low
Reserved
Local reference
reference site = REMOTE -> auto
on pressed & active
Reserved
Protection mode notification
Reserved
Unused
Reserved
Unused
Unused
Motor
Power Limit
Unused
Generator
Reserved
Unused
Unused
BackEMF too
Unused
high
PTC thermi-
Unused
stor (W74)
Protection mode
Remove the wiring from terminal 50. If the
warning clears, the problem is with the wiring. If
the warning does not clear, replace the control
card.
MG33MO02