Parameter Descriptions

3.16 Parameters: 15-** Drive Information

3.16.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
[0 - 2147483647
View how many hours the frequency
*
h]
converter has run. The value is saved
when the frequency converter is turned
off.
15-01 Running Hours
Range:
Function:
0 h
[0 -
View how many hours the motor has
*
2147483647 h]
run. Reset the counter in 15-07 Reset
Running Hours Counter. The value is
saved when the frequency converter is
turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
[0 - 2147483647
Registering the power consumption
*
kWh]
of the motor as a mean value over
one hour. Reset the counter in
15-06 Reset kWh Counter.
15-03 Power Up's
Range:
Function:
0
[0 - 2147483647 ] View the number of times the frequency
*
converter has been powered up.
15-04 Over Temp's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
temperature faults which have occurred.
15-05 Over Volt's
Range:
Function:
0
[0 - 65535 ] View the number of frequency converter
*
overvoltages which have occurred.
15-06 Reset kWh Counter
Option:
Function:
[0] Do not reset
No reset of the kWh counter is desired.
[1] Reset counter Press [OK] to reset the kWh counter to zero
(see 15-02 kWh Counter).
NOTICE
The reset is carried out by pressing [OK].
®
VLT
AutomationDrive FC 301/302 Programming Guide
15-07 Reset Running Hours Counter
Option:
[0]
Do not
*
reset
[1]
Reset
counter
3.16.2 15-1* Data Log Settings
The Data Log enables continuous logging of up to 4 data
sources (15-10 Logging Source) at individual rates
(15-11 Logging Interval). A trigger event (15-12 Trigger
Event) and window (15-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
15-10 Logging Source
Array [4]
Option:
[0]
*
[15]
[1472] Legacy Alarm Word
[1473] Legacy Warning Word
[1474] Leg. Ext. Status Word
[1600] Control Word
[1601] Reference [Unit]
[1602] Reference %
[1603] Status Word
[1610] Power [kW]
[1611] Power [hp]
[1612] Motor Voltage
[1613] Frequency
[1614] Motor current
[1616] Torque [Nm]
[1617] Speed [RPM]
[1618] Motor Thermal
[1621] Torque [%] High Res.
[1622] Torque [%]
[1624] Calibrated Stator Resistance
[1625] Torque [Nm] High
[1630] DC Link Voltage
[1632] Brake Energy /s
[1633] Brake Energy /2 min
[1634] Heatsink Temp.
[1635] Inverter Thermal
[1648] Speed Ref. After Ramp [RPM]
[1650] External Reference
[1651] Pulse Reference
[1652] Feedback[Unit]
MG33MH02 - Rev. 2013-09-30
Function:
Select [1] Reset and press [OK] to reset the
Running Hours counter to zero (see
15-01 Running Hours). This parameter cannot
be selected via the serial port, RS-485.
Select [0] Do not reset if no reset of the
Running Hours counter is desired.
Function:
Select which variables are
to be logged.
None
Readout: actual setup
3
3
141