Parameter Descriptions
3.9.5 8-5* Digital/Bus
Parameters for configuring the control word merging.
NOTICE
These parameters are active only when
parameter 8-01 Control Site is set to [0] Digital and control
word.
8-50 Coasting Select
Select the trigger for the coasting function.
Option:
Function:
[0]
Digital input A digital input triggers the coasting function.
[1]
Bus
A serial communication port or the fieldbus
triggers the coasting function.
[2]
Logic AND
The fieldbus/serial communication port and a
digital input trigger the coasting function.
[3]
Logic OR
The fieldbus/serial communication port or a
*
digital input triggers the coasting function.
8-51 Quick Stop Select
Select the trigger for the quick stop function.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-52 DC Brake Select
Select control of the DC brake via the terminals (digital input)
and/or via the fieldbus.
Option:
Function:
NOTICE
When parameter 1-10 Motor Construction
is set to [1] PM non-salient SPM, only
selection [0] Digital input is available.
[0] Digital input Activate a start command via a digital input.
[1] Bus
Activate a start command via the serial
communication port or fieldbus option.
[2] Logic AND
Activate a start command via the fieldbus/serial
communication port and also via 1 of the
digital inputs.
[3] Logic OR
Activate a start command via the fieldbus/serial
communication port or via 1 of the digital
inputs.
8-53 Start Select
Select the trigger for the start function.
Option:
Function:
[0]
Digital input A digital input triggers the start function.
MG33MO02
Programming Guide
8-53 Start Select
Select the trigger for the start function.
Option:
[1]
[2]
[3]
*
8-54 Reversing Select
Select the trigger for the reversing function.
Option:
[0]
[1]
[2]
[3]
*
8-55 Set-up Select
Function:
Select the trigger for the set-up selection.
Option:
[0]
[1]
[2]
[3]
*
8-56 Preset Reference Select
Option:
[0]
[1]
[2]
[3]
*
Danfoss A/S © 01/2018 All rights reserved.
Function:
Bus
A serial communication port or the fieldbus
triggers the start function.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the start function.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the start function.
Function:
Digital input A digital input triggers the reversing function.
Bus
A serial communication port or the fieldbus
triggers the reversing function.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the reversing function.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the reversing function.
Function:
Digital input A digital input triggers the set-up selection.
Bus
A serial communication port or the fieldbus
triggers the set-up selection.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the set-up selection.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the set-up selection.
Function:
Select the trigger for the preset reference
selection.
Digital
A digital input triggers the preset reference
input
selection.
Bus
A serial communication port or the fieldbus
triggers the preset reference selection.
Logic AND
The fieldbus/serial communication port and a
digital input trigger the preset reference
selection.
Logic OR
The fieldbus/serial communication port or a
digital input triggers the preset reference
selection.
3
3
141