Parameters: 6-** Analog In/Out - Danfoss VLT AutomationDrive FC 301 Programming Manual

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions

3.7 Parameters: 6-** Analog In/Out

3.7.1 6-0* Analog I/O Mode
The analog inputs can be allocated to be either voltage
(FC 301: 0–10 V, FC 302: 0 to ±10 V) or current input (FC
3
3
301/FC 302: 0/4–20 mA).
NOTICE
Thermistors may be connected to either an analog or a
digital input.
6-00 Live Zero Timeout Time
Range:
10
[1 -
Enter the live zero timeout in s. Live zero timeout
s
99 s]
time is active for analog inputs, that is terminal 53
*
or terminal 54, used as reference or feedback
sources.
If the reference signal value associated with the
selected current input drops below 50% of the
value set in
for a time period longer than the time set in
parameter 6-00 Live Zero Timeout Time, the function
selected in parameter 6-01 Live Zero Timeout
Function is activated.
6-01 Live Zero Timeout Function
Option:
[0]
Off
*
112
Function:
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-12 Terminal 53 Low Current
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-22 Terminal 54 Low Current
Function:
Select the timeout function. If the input signal
on terminal 53 or 54 is below 50% of the value
in
Parameter 6-10 Terminal 53 Low Voltage
Parameter 6-12 Terminal 53 Low Current
Parameter 6-20 Terminal 54 Low Voltage
Parameter 6-22 Terminal 54 Low Current
for a time period defined in parameter 6-00 Live
Zero Timeout Time, then the function set in
parameter 6-01 Live Zero Timeout Function is
activated.
If several timeouts occur simultaneously, the
frequency converter prioritizes the timeout
functions as follows:
1.
Parameter 6-01 Live Zero Timeout
Function.
2.
Parameter 8-04 Control Word Timeout
Function.
Danfoss A/S © 01/2018 All rights reserved.
®
VLT
AutomationDrive FC 301/302
6-01 Live Zero Timeout Function
Option:
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max.
speed
[5]
Stop and
trip
[20] Coast
[21] Coast and
trip
3.7.2 6-1* Analog Input 1
Parameters for configuring the scaling and limits for analog
input 1 (terminal 53).
Par 6-xx
'High Ref./
Feedb. Value'
Par 6-xx
'Low Ref./
Feedb. Value'
Illustration 3.43 Analog Input 1
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
6-11 Terminal 53 High Voltage
Range:
10 V
*
- 10 V]
Function:
Frozen at the present value.
Overruled to stop.
Overruled to jog speed.
Overruled to maximum speed.
Overruled to stop with subsequent trip.
Ref./Feedback
[RPM]
1500
1200
900
600
300
150
Ex.
1 V
5 V
Par 6-xx
Par 6-xx
'Low Voltage'or
'High Voltage'or
'Low Current'
'High Current'
Function:
[-10.00 -
Enter the low voltage value. This analog
par. 6-11 V]
input scaling value should correspond to
the minimum reference value set in
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value.
Function:
[ par. 6-10
Enter the high voltage value. This analog
input scaling value should correspond to the
high reference feedback value set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value.
10 V
Analog input
MG33MO02