Danfoss VLT AutomationDrive FC 301 Programming Manual page 149

Hide thumbs Also See for VLT AutomationDrive FC 301:
Table of Contents

Advertisement

Parameter Descriptions
13-10 Comparator Operand
Option:
Function:
[69]
Above I high
The motor current is higher than the
value in parameter 4-51 Warning Current
High.
[70]
Out of speed
The speed is outside the range set in
range
parameter 4-52 Warning Speed Low and
parameter 4-53 Warning Speed High.
[71]
Below speed
The output speed is lower than the value
low
in parameter 4-52 Warning Speed Low.
[72]
Above speed
The output speed is higher than the
high
value in parameter 4-53 Warning Speed
High.
[75]
Out of feedback
The feedback is outside the range set in
range
parameter 4-56 Warning Feedback Low
and parameter 4-57 Warning Feedback
High.
[76]
Below feedback
The feedback is lower than the limit set
low
in parameter 4-56 Warning Feedback Low.
[77]
Above feedback
The feedback exceeds the limit set in
high
parameter 4-57 Warning Feedback High.
[80]
Thermal
This operand becomes true when the
warning
frequency converter detects any thermal
warning, for instance when the
temperature exceeds the limit in the
motor, the frequency converter, the brake
resistor, or thermistor.
[82]
Mains out of
The mains voltage is outside the
range
specified voltage range.
[85]
Warning
If a warning is triggered, this operand
gets the warning number.
[86]
Alarm (trip)
A trip alarm is active.
[87]
Alarm (trip lock) A trip lock alarm is active.
[90]
Bus OK
Active communication (no timeout) via
the serial communication port.
[91]
Torque limit &
If the frequency converter has received a
stop
stop signal and is at the torque limit, the
signal is logic 0.
[92]
Brake fault
The brake IGBT is short-circuited.
(IGBT)
[93]
Mech. brake
The mechanical brake is active.
control
[94]
Safe stop active
[100] Comparator 0
The result of comparator 0.
[101] Comparator 1
The result of comparator 1.
[102] Comparator 2
The result of comparator 2.
[103] Comparator 3
The result of comparator 3.
[104] Comparator 4
The result of comparator 4.
[105] Comparator 5
The result of comparator 5.
MG33MO02
Programming Guide
13-10 Comparator Operand
Option:
[110] Logic rule 0
[111] Logic rule 1
[112] Logic rule 2
[113] Logic rule 3
[114] Logic rule 4
[115] Logic rule 5
[120] SL Time-out 0
[121] SL Time-out 1
[122] SL Time-out 2
[123] SL Time-out 3
[124] SL Time-out 4
[125] SL Time-out 5
[126] SL Time-out 6
[127] SL Time-out 7
[130] Digital input
DI18
[131] Digital input
DI19
[132] Digital input
DI27
[133] Digital input
DI29
[134] Digital input
DI32
[135] Digital input
DI33
[150] SL digital
output A
[151] SL digital
output B
[152] SL digital
output C
[153] SL digital
output D
[154] SL digital
output E
[155] SL digital
output F
[160] Relay 1
[161] Relay 2
[162] Relay 3
[163] Relay 4
[164] Relay 5
[165] Relay 6
[166] Relay 7
[167] Relay 8
[168] Relay 9
Danfoss A/S © 01/2018 All rights reserved.
Function:
The result of logic rule 0.
The result of logic rule 1.
The result of logic rule 2.
The result of logic rule 3.
The result of logic rule 4.
The result of logic rule 5.
The result of SLC timer 0.
The result of SLC timer 1.
The result of SLC timer 2.
The result of SLC timer 3.
The result of SLC timer 4.
The result of SLC timer 5.
The result of SLC timer 6.
The result of SLC timer 7.
Digital input 18 (high=true).
Digital input 19 (high=true).
Digital input 27 (high=true).
Digital input 29 (high=true).
Digital input 32 (high=true).
Digital input 33 (high=true).
Use the result of the SLC output A.
Use the result of the SLC output B.
Use the result of the SLC output C.
Use the result of the SLC output D.
Use the result of the SLC output E.
Use the result of the SLC output F.
Relay 1 is active.
Relay 2 is active.
3
3
147