Parameter Descriptions
13-40 Logic Rule Boolean 1
Option:
Function:
[102] Relay 1
[103] Relay 2
[104] Relay 3
X47/VLT
113.
[105] Relay 4
X47/VLT
113.
[106] Relay 5
X47/VLT
113.
[107] Relay 6
X47/VLT
113.
[108] Relay 7
X34/VLT
[109] Relay 8
X34/VLT
[110] Relay 9
X34/VLT
NOTICE
[222] Homing Ok
This option is available only with
software version 48.20 and
newer.
Homing is completed with the
selected homing function
(parameter 17-80 Homing Function).
NOTICE
[223] On Target
This option is available only with
software version 48.20 and
newer.
Positioning is completed and the on
target signal is sent when the actual
position is within parameter 3-05 On
Reference Window for the duration of
parameter 3-09 On Target Time and the
actual speed does not exceed
parameter 3-05 On Reference Window.
NOTICE
[224] Position Error
This option is available only with
software version 48.20 and
newer.
The position error exceeds the value
in parameter 4-71 Maximum Position
Error for the time set in
parameter 4-72 Position Error Timeout.
NOTICE
[225] Position Limit
This option is available only with
software version 48.20 and
newer.
MG33MO02
Programming Guide
®
Extended Relay Card MCB
®
Extended Relay Card MCB
®
Extended Relay Card MCB
®
Extended Relay Card MCB
®
Relay Card MCB 105.
®
Relay Card MCB 105.
®
Relay Card MCB 105.
Danfoss A/S © 01/2018 All rights reserved.
13-40 Logic Rule Boolean 1
Option:
Function:
The position is outside the limits set
in parameter 3-06 Minimum Position
and parameter 3-07 Maximum Position.
NOTICE
[226] Touch on Target
This option is available only with
software version 48.20 and
newer.
Target position is reached in touch
probe position mode.
NOTICE
[227] Touch Activated
This option is available only with
software version 48.20 and
newer.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the 1
st
logical operator to use on the
boolean inputs from parameter 13-40 Logic Rule
Boolean 1 and parameter 13-42 Logic Rule
Boolean 2.
Parameter numbers in square brackets stand
for the boolean inputs of parameters in
parameter group 13-** Smart Logic Control.
[0] DISABLED
Ignores:
Parameter 13-42 Logic Rule Boolean 2.
Parameter 13-43 Logic Rule Operator 2.
Parameter 13-44 Logic Rule Boolean 3.
[1] AND
Evaluates the expression [13-40] AND [13-42].
[2] OR
Evaluates the expression [13-40] OR [13-42].
[3] AND NOT
Evaluates the expression [13-40] AND NOT
[13-42].
[4] OR NOT
Evaluates the expression [13-40] OR NOT
[13-42].
[5] NOT AND
Evaluates the expression NOT [13-40] AND
[13-42].
[6] NOT OR
Evaluates the expression NOT [13-40] OR
[13-42].
[7] NOT AND
Evaluates the expression NOT [13-40] AND NOT
NOT
[13-42].
[8] NOT OR
Evaluates the expression NOT [13-40] OR NOT
NOT
[13-42].
3
3
155