Parameter Descriptions
35-16 Term. X48/4 Low Temp. Limit
Range:
Size related
*
35-17]
3
3
35-17 Term. X48/4 High Temp. Limit
Range:
Size related
*
204]
3.25.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
35-25 Term. X48/7 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/7. Set the temperature
limits in parameter 35-26 Term. X48/7 Low Temp. Limit and
parameter 35-27 Term. X48/7 High Temp. Limit.
Option:
[0]
*
[1]
35-26 Term. X48/7 Low Temp. Limit
Range:
Size related
*
35-27]
35-27 Term. X48/7 High Temp. Limit
Range:
Size related
*
204]
214
Function:
[ -50 - par.
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
[ par. 35-16 -
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/4.
Function:
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/7. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Function:
Disabled
Enabled
Function:
[ -50 - par.
Enter the minimum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
Function:
[ par. 35-26 -
Enter the maximum temperature
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/7.
Danfoss A/S © 01/2018 All rights reserved.
®
VLT
AutomationDrive FC 301/302
3.25.4 35-3* Temp. Input X48/10 (MCB 114)
35-34 Term. X48/10 Filter Time Constant
Range:
0.001 s
*
35-35 Term. X48/10 Temp. Monitor
This parameter facilitates the possibility of enabling or disabling
the temperature monitor for terminal X48/10. Set the
temperature limits in parameter 35-36 Term. X48/10 Low Temp.
Limit/parameter 35-37 Term. X48/10 High Temp. Limit.
Option:
[0]
*
[1]
35-36 Term. X48/10 Low Temp. Limit
Range:
Size related
35-37 Term. X48/10 High Temp. Limit
Range:
Size related
3.25.5 35-4* Analog Input X48/2 (MCB 114)
35-42 Term. X48/2 Low Current
Range:
4 mA
*
35-43 Term. X48/2 High Current
Range:
20 mA
*
Function:
[0.001 - 10
Enter the filter time constant. This is a
s]
first-order digital low-pass filter time
constant for suppressing electrical noise
in terminal X48/10. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Disabled
Enabled
Function:
[ -50 - par.
Enter the minimum temperature
*
35-37]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
Function:
[ par. 35-36 -
Enter the maximum temperature
*
204]
reading that is expected for
normal operation of the
temperature sensor at terminal
X48/10.
Function:
[ 0 - par.
Enter the current (mA) that corresponds to
35-43 mA]
the low reference value, set in
parameter 35-44 Term. X48/2 Low Ref./Feedb.
Value. The value must be more than 2 mA to
activate the live zero timeout function in
parameter 6-01 Live Zero Timeout Function.
Function:
[ par. 35-42 -
Enter the current (mA) that corresponds
20 mA]
to the high reference value (set in
parameter 35-45 Term. X48/2 High Ref./
Feedb. Value).
Function:
MG33MO02