Parameter Descriptions
13-51 SL Controller Event
Option:
[226] Touch on Target
3
3
[227] Touch Activated
13-52 SL Controller Action
Option:
[0]
DISABLED
[1]
No action
[2]
Select set-up
1
[3]
Select set-up
2
[4]
Select set-up
3
[5]
Select set-up
4
[10]
Select preset
ref 0
162
®
VLT
AutomationDrive FC 301/302
Function:
NOTICE
This option is available only with
software version 48.20 and
newer.
Target position is reached in touch
probe position mode.
NOTICE
This option is available only with
software version 48.20 and
newer.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
Function:
Select the action corresponding to the SLC
event. Actions are executed when the
corresponding event (defined in
parameter 13-51 SL Controller Event) is
evaluated as true.
Changes the active set-up
(parameter 0-10 Active Set-up) to 1.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
Changes the active set-up
parameter 0-10 Active Set-up) to 2.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
Changes the active set-up
(parameter 0-10 Active Set-up) to 3.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
Changes the active set-up
(parameter 0-10 Active Set-up) to 4.
If the set-up is changed, it merges with
other set-up commands coming from
either the digital inputs or via a fieldbus.
Selects preset reference 0.
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
Danfoss A/S © 01/2018 All rights reserved.
13-52 SL Controller Action
Option:
Function:
[11]
Select preset
Selects preset reference 1.
ref 1
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[12]
Select preset
Selects preset reference 2.
ref 2
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[13]
Select preset
Selects preset reference 3.
ref 3
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[14]
Select preset
Selects preset reference 4.
ref 4
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[15]
Select preset
Selects preset reference 5.
ref 5
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[16]
Select preset
Selects preset reference 6.
ref 6
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[17]
Select preset
Selects preset reference 7.
ref 7
If the active preset reference is changed, it
merges with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[18]
Select ramp 1 Selects ramp 1.
[19]
Select ramp 2 Selects ramp 2.
[20]
Select ramp 3 Selects ramp 3.
[21]
Select ramp 4 Selects ramp 4.
[22]
Run
Issues a start command to the frequency
converter.
[23]
Run reverse
Issues a start reverse command to the
frequency converter.
[24]
Stop
Issues a stop command to the frequency
converter.
[25]
Qstop
Issues a quick stop command to the
frequency converter.
[26]
Dcstop
Issues a DC stop command to the
frequency converter.
MG33MO02