Parameter Descriptions
14-74 VLT Ext. Status Word
Range:
0 N/A
[0 - 4294967295 N/A] Readout of the external status
*
3.14.10 14-8* Options
14-80 Option Supplied by External 24VDC
Option:
Function:
NOTICE
This parameter is only changing function by
performing a power cycle.
[0]
No
Select [0] No to use the frequency converter's 24 V DC
supply.
[1]
Yes Select [1] Yes if a 24 V DC external supply is used to
*
power the option. Inputs/outputs are galvanically
isolated from the frequency converter when operated
from an external supply.
14-88 Option Data Storage
Range:
Function:
0
[0 - 65535] This parameter stores information about options
*
over a power cycle.
14-89 Option Detection
Selects the behavior of the frequency converter when a change
in the option configuration is detected.
Option:
Function:
[0]
Protect Option
Freezes the current settings and
*
Config.
prevents unwanted changes when
missing or defective options are
detected.
[1]
Enable Option
Changes frequency converter settings
Change
and is used when modifying the
system configuration. This parameter
MG33MO02
Programming Guide
Function:
word corresponding to VLT 5000.
Danfoss A/S © 01/2018 All rights reserved.
14-89 Option Detection
Selects the behavior of the frequency converter when a change
in the option configuration is detected.
Option:
Function:
setting returns to [0] Protect Option
Config. after an option change.
3.14.11 14-9* Fault Settings
14-90 Fault Level
This is an array parameter with 26 elements. Each of the bits can
be configured to any of the following options. Use this
parameter to customize fault levels.
Option:
Function:
[0] Off
Use [0] Off with caution as it ignores all
warnings and alarms for the selected
source.
[1] Warning
[2] Trip
Changing a fault level from default option
[3] Trip Lock to [2] Trip leads to the
automatic reset of the alarm. For alarms
involving overcurrent, the frequency
converter has a hardware protection that
issues a 3-minute recovery after 2
consecutive overcurrent incidents. This
hardware protection cannot be overruled.
[3] Trip Lock
[4] Trip w. delayed
This option adds a delay between
reset
automatic resets, otherwise it is the same
as option [2] Trip. The delay prevents a
situation where reset is attempted
repeatedly for an overcurrent situation.
Hardware protection of the frequency
converter forces the 3-minute recovery time
after 2 consecutive overcurrents (within a
short time window).
3
3
175