Parameter Descriptions
16-25 Torque [Nm] High
Range:
Function:
0.0
[-200000000.0
View the torque value with sign, applied
Nm
- 200000000.0
to the motor shaft. Some motors supply
*
Nm]
more than 160% torque. Therefore, the
minimum value and the maximum value
depend on the maximum motor current
as well as the motor used. This specific
readout has been adapted to be able to
show higher values than the standard
readout in parameter 16-16 Torque [Nm].
3.16.3 16-3* Drive Status
16-30 DC Link Voltage
Range:
Function:
0 V
[0 - 10000 V] View a measured value. The value is filtered
*
with a 30 ms time constant.
16-31 System Temp.
Range:
Function:
NOTICE
0 °C
[-128 -
127 °C]
*
Valid for FC 302 only.
Shows the highest internal system temperature.
In the smaller enclosure sizes (A–C), the system
temperature matches the control card
temperature measurement in
parameter 16-39 Control Card Temp. In the larger
enclosure sizes (D–F), the system temperature is
the highest temperature measured on hardware
components with temperature sensors, for
example, the power card(s).
16-32 Brake Energy /s
Range:
Function:
0 kW
[0 - 10000 kW] View the brake power transmitted to an
*
external brake resistor, stated as an
instant value.
16-33 Brake Energy Average
Range:
Function:
0 kW
[0 - 10000
View the brake power transmitted to an
*
kW]
external brake resistor. The mean power is
calculated on an average level based on the
selected time period within
parameter 2-13 Brake Power Monitoring.
16-34 Heatsink Temp.
Range:
Function:
0 °C
[0 -
View the frequency converter heat sink
*
temperature. The cutout limit is 90 ±5 °C (194
255 °C]
MG33MO02
Programming Guide
16-34 Heatsink Temp.
Range:
16-35 Inverter Thermal
Range:
0 %
*
16-36 Inv. Nom. Current
Range:
10.00 A
*
16-37 Inv. Max. Current
Range:
16.00 A
*
16-38 SL Controller State
Range:
0 N/A
*
16-39 Control Card Temp.
Range:
0 °C
*
16-40 Logging Buffer Full
Option:
[0]
No
*
[1]
Yes
16-41 Performance Measurements
Range:
0
*
16-42 Service Log Counter
Range:
0
[ 0 -
*
24]
Danfoss A/S © 01/2018 All rights reserved.
Function:
±9 °F), and the motor cuts back in at 60
±5 °C (140 ±9 °F).
Function:
[0 - 100 %]
View the percentage load on the inverter.
Function:
[0.01 -
View the inverter nominal current,
10000.00 A]
which must match the nameplate data
on the connected motor. The data is
used for calculation of torque, motor
overload protection, and so on.
Function:
[0.01 -
View the inverter maximum current,
10000.00 A]
which must match the nameplate data
on the connected motor. The data is
used for calculation of torque, motor
overload protection, and so on.
Function:
[0 - 100 N/A] View the state of the event under
execution by the SL controller.
Function:
[0 - 100 °C] View the temperature on the control card,
stated in °C.
Function:
View whether the logging buffer is full (see
chapter 3.15.2 15-1* Data Log Settings). The logging
buffer is never full when parameter 15-13 Logging
Mode is set to [0] Log always.
[0 - 2147483647 ]
Function:
Shows the number of service logs stored in the
ServiceLog file. If the ServiceLog file is full, clear the
logged data by selecting option [5] Clear service logs
3
Function:
187
3