Parameter Descriptions
13-43 Logic Rule Operator 2
Array [6]
Option:
3
3
[0] DISABLED
[1] AND
[2] OR
[3] AND NOT
[4] OR NOT
[5] NOT AND
[6] NOT OR
[7] NOT AND
NOT
[8] NOT OR NOT
13-44 Logic Rule Boolean 3
Array [6]
Option:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed low
158
®
VLT
Function:
Select the 2
nd
logical operator to be used on
the boolean input calculated in:
Parameter 13-40 Logic Rule Boolean 1.
Parameter 13-41 Logic Rule Operator
1.
Parameter 13-42 Logic Rule Boolean 2.
[13-44] signifies the boolean input of
parameter 13-44 Logic Rule Boolean 3.
[13-40/13-42] signifies the boolean input
calculated in:
Parameter 13-40 Logic Rule Boolean 1.
Parameter 13-41 Logic Rule Operator
1.
Parameter 13-42 Logic Rule Boolean 2.
Select this option to ignore
parameter 13-44 Logic Rule Boolean 3.
Function:
Select the 3
rd
boolean (true or false)
input for the selected logic rule. See
parameter 13-01 Start Event (options
[0] False–[61] Logic rule 5) and
parameter 13-02 Stop Event (options
[70] SL Time-out 3–[75] Start command
given) for more information.
Danfoss A/S © 01/2018 All rights reserved.
AutomationDrive FC 301/302
13-44 Logic Rule Boolean 3
Array [6]
Option:
[12]
Above speed high
[13]
Out of feedb.
range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
[21]
Alarm (trip lock)
[22]
Comparator 0
[23]
Comparator 1
[24]
Comparator 2
[25]
Comparator 3
[26]
Logic rule 0
[27]
Logic rule 1
[28]
Logic rule 2
[29]
Logic rule 3
[30]
SL Time-out 0
[31]
SL Time-out 1
[32]
SL Time-out 2
[33]
Digital input DI18
[34]
Digital input DI19
[35]
Digital input DI27
[36]
Digital input DI29
[37]
Digital input DI32
[38]
Digital input DI33
[39]
Start command
[40]
Drive stopped
[41]
Reset Trip
[42]
Auto-reset Trip
[43]
Ok key
[44]
Reset key
[45]
Left key
[46]
Right key
[47]
Up key
[48]
Down key
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
Function:
[OK] is pressed. Only available on the
graphical LCP.
[Reset] is pressed. Only available on
the graphical LCP.
[◄] is pressed. Only available on the
graphical LCP.
[►] is pressed. Only available on the
graphical LCP.
[
] is pressed. Only available on the
graphical LCP.
[
] is pressed. Only available on the
graphical LCP.
MG33MO02