Parameter Descriptions
16-96 Maintenance Word
Range:
3
3
192
®
VLT
Function:
•
Bit 13: Maintenance Text 0.
•
Bit 14: Maintenance Text 1.
•
Bit 15: Maintenance Text 2.
•
Bit 16: Maintenance Text 3.
•
Bit 17: Maintenance Text 4.
•
Bit 25: Service log full.
Position
Valve
Fan
Pump
4⇒
bea-
bea-
rings
rings
Position
Pump
Tempe-
Flow
3⇒
seals
rature
trans-
trans-
mitter
mitter
Position
Drive
Drive
Filter
2⇒
system
cooling
health
fan
check
Position
–
–
–
1⇒
0
–
–
–
hex
1
–
–
–
hex
2
–
–
+
hex
3
–
–
+
hex
4
–
+
–
hex
5
–
+
–
hex
6
–
+
+
hex
7
–
+
+
hex
8
+
–
–
hex
9
+
–
–
hex
A
+
–
+
hex
B
+
–
+
hex
C
+
+
–
hex
D
+
+
–
hex
E
+
+
+
hex
F
+
+
+
hex
Table 3.32 Maintenance Word
Example:
The preventive maintenance word shows
040Ahex.
Position
1
2
3
Hex value
0
4
0
Table 3.33 Example
The 1st digit 0 indicates that no items from
th
the 4
row require maintenance.
nd
rd
The 2
digit 4 refers to the 3
row indicating
that the frequency converter cooling fan
requires maintenance.
Danfoss A/S © 01/2018 All rights reserved.
AutomationDrive FC 301/302
16-96 Maintenance Word
Range:
Motor
bea-
rings
Pres-
sure
trans-
mitter
Fan
belt
War-
ranty
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
4
A
Function:
rd
The 3
digit 0 indicates that no items from
the 2
nd
row require maintenance.
th
The 4
digit A refers to the top row
indicating that the valve and the pump
bearings require maintenance.
MG33MO02