Parameter Descriptions

3.17 Parameters: 17-** Feedback

More parameters to configure the feedback from the
®
encoder (VLT
Encoder Input MCB 102), resolver (VLT
Resolver Input MCB 103), or the frequency converter itself.
3.17.1 17-1* Inc. Enc. Interface
Parameters in this group configure the incremental
®
interface of the VLT
Encoder Input MCB 102. Both the
incremental and absolute interfaces are active at the same
time.
NOTICE
Do not use incremental encoders with PM motors. In a
closed-loop control, consider absolute encoders or
resolvers.
NOTICE
These parameters cannot be adjusted while the motor is
running.
17-10 Signal Type
Select the incremental type (A/B channel) of the encoder in use.
Find the information on the encoder datasheet.
Select [0] None if the feedback sensor is an absolute encoder
only.
Option:
[0]
None
[1]
RS422 (5V TTL)
*
[2]
Sinusoidal 1Vpp
17-11 Resolution (PPR)
Range:
Function:
1024 N/A
[10 - 10000
Enter the resolution of the
*
N/A]
incremental track, that is the
number of pulses or periods per
revolution.
3.17.2 17-2* Abs. Enc. Interface
Parameters in this group configure the absolute interface
®
of the VLT
Encoder Input MCB 102. Both the incremental
and absolute interfaces are active at the same time.
17-20 Protocol Selection
Option:
Function:
NOTICE
This parameter cannot be adjusted while
the motor is running.
[0]
None
Select [0] None if the feedback sensor is an
*
incremental encoder only.
MG33MO02
Programming Guide
17-20 Protocol Selection
Option:
[1]
®
[2]
[4]
17-21 Resolution (Positions/Rev)
Range:
8192.
N/A
*
17-22 Multiturn Revolutions
Range:
1
*
17-24 SSI Data Length
Range:
13 N/A
17-25 Clock Rate
Function:
Range:
0 kHz
17-26 SSI Data Format
Option:
[0]
*
[1]
17-34 HIPERFACE Baudrate
Option:
[0]
[1]
[2]
[3]
[4]
*
[5]
Danfoss A/S © 01/2018 All rights reserved.
Function:
HIPERFACE Select [1] HIPERFACE if the encoder is absolute
only.
EnDat
SSI
Function:
[4. -
Select the resolution of the absolute
131072. N/A]
encoder, that is the number of counts
per revolution.
The value depends on setting in
parameter 17-20 Protocol Selection.
Function:
[1 - 16777216] Select the number of multi-turn revolutions.
Select value 1 for single-turn type encoders.
Function:
[13 - 25
Set the number of bits for the SSI
*
N/A]
telegram. Select 13 bits for single-turn
encoders and 25 bits for multi-turn
encoders.
Function:
[100 - 0 kHz] Set the SSI clock rate. With long encoder
*
cables, the clock rate must be reduced.
Function:
Gray code
Binary code
Set the data format of the SSI data.
Function:
NOTICE
This parameter cannot be adjusted while the
motor is running.
Select the baud rate of the attached encoder.
The parameter is only accessible when
parameter 17-20 Protocol Selection is set to [1]
HIPERFACE.
600
1200
2400
4800
9600
19200
3
3
193