Parameter Descriptions
13-11 Comparator Operator
Option:
Function:
[1]
≈ (equal)
The result of the evaluation is true when the
variable selected in parameter 13-10 Comparator
*
Operand is approximately equal to the fixed
value in parameter 13-12 Comparator Value.
[2]
>
Inverse logic of option [0] <.
[5]
TRUE
longer
than..
[6]
FALSE
longer
than..
[7]
TRUE
shorter
than..
[8]
FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range:
Size
[-100000 -
Enter the trigger level for the
related
100000 ]
variable that is monitored by this
*
comparator. This is an array
parameter containing comparator
values 0–5.
3.13.3 RS Flip Flops
The reset/set flip flops hold the signal until set/reset.
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
Illustration 3.55 Reset/Set Flip Flops
2 parameters are used, and the output can be used in the
logic rules and as events.
S
R
Flip Flop Output
Illustration 3.56 Flip Flop Outputs
MG33MO02
Programming Guide
Function:
Danfoss A/S © 01/2018 All rights reserved.
The 2 operators can be selected from a long list. As a
special case, the same digital input can be used as both
set and reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input (for example, DI32) as start/
stop.
Parameter
Setting
Parameter 13-00 SL Controller
On
Mode
Parameter 13-01 Start Event
True
Parameter 13-02 Stop Event
False
Parameter 13-40 Logic Rule
[37] Digital
Boolean 1 [0]
Input DI32
Parameter 13-42 Logic Rule
[2] Running –
Boolean 2 [0]
Parameter 13-41 Logic Rule
[3] AND
Operator 1 [0]
NOT
Parameter 13-40 Logic Rule
[37] Digital
Boolean 1 [1]
Input DI32
Parameter 13-42 Logic Rule
[2] Running –
Boolean 2 [1]
Parameter 13-41 Logic Rule
[1] AND
Operator 1 [1]
Parameter 13-15 RS-FF Operand
[26] Logic
S [0]
rule 0
Parameter 13-16 RS-FF Operand
[27] Logic
R [0]
rule 1
Parameter 13-51 SL Controller
[94] RS
Event [0]
Flipflop 0
Parameter 13-52 SL Controller
[22] Run
Action [0]
Parameter 13-51 SL Controller
[27] Logic
Event [1]
rule 1
Parameter 13-52 SL Controller
[24] Stop
Action [1]
Table 3.26 Operators
13-15 RS-FF Operand S
Option:
Function:
[0]
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
3
Notes
Output from
parameter 13-41 Log
ic Rule Operator 1
[0].
Output from
parameter 13-41 Log
ic Rule Operator 1
[1].
Output from
parameter 13-15 RS-
FF Operand S and
parameter 13-16 RS-
FF Operand R.
149