Parameter Descriptions
3.8 Parameters: 7-** Controllers
3.8.1 7-0* Speed PID Ctrl.
NOTICE
If separate encoders are used (FC 302 only), adjust the
ramp-related parameters according to the gear ratio
between the 2 encoders.
7-00 Speed PID Feedback Source
Option:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
Select the encoder for closed-loop
feedback.
The feedback may come from a
different encoder (typically mounted
on the application itself ) than the
motor-mounted encoder feedback
selected in parameter 1-02 Flux Motor
Feedback Source.
[0]
Motor feedb. P1-02
*
[1]
24V encoder
[2]
MCB 102
[3]
MCB 103
[5]
MCO Encoder 2
[6]
Analog input 53
[7]
Analog input 54
[8]
Frequency input 29
[9]
Frequency input 33
MG33MO02