Parameter Descriptions
5-40 Function Relay
Option:
Function:
[197] RS Flipflop 5
See parameter group 13-1*
Comparators.
[198] RS Flipflop 6
See parameter group 13-1*
Comparators.
[199] RS Flipflop 7
See parameter group 13-1*
Comparators.
NOTICE
[222] Homing Ok
This option is available only with
software version 48.XX.
Homing is completed with the selected
homing function
(parameter 17-80 Homing Function).
NOTICE
[223] On Target
This option is available only with
software version 48.XX.
Positioning is completed and the on
target signal is sent when the actual
position is within parameter 3-05 On
Reference Window for the duration of
parameter 3-09 On Target Time and the
actual speed does not exceed
parameter 3-05 On Reference Window.
NOTICE
[224] Position Error
This option is available only with
software version 48.XX.
The position error exceeds the value in
parameter 4-71 Maximum Position Error
for the time set in
parameter 4-72 Position Error Timeout.
NOTICE
[225] Position Limit
This option is available only with
software version 48.XX.
The position is outside the limits set in
parameter 3-06 Minimum Position and
parameter 3-07 Maximum Position.
NOTICE
[226] Touch on Target
This option is available only with
software version 48.XX.
Target position is reached in touch
probe position mode.
NOTICE
[227] Touch Activated
This option is available only with
software version 48.XX.
Touch probe positioning active. The
frequency converter monitors the
touch probe sensor input.
MG33MO02
Programming Guide
5-41 On Delay, Relay
Array [20]
Range:
0.01 s
*
Selected
Event
Relay
output
Selected
Event
Relay
output
Illustration 3.37 On Delay, Relay
5-42 Off Delay, Relay
Array[20]
Range:
0.01 s
*
Selected
Event
Relay
output
Illustration 3.38 Off Delay, Relay
If the selected event condition changes before the on
delay or off delay timer expires, the relay output is
unaffected.
Danfoss A/S © 01/2018 All rights reserved.
Function:
[0.01 -
Enter the delay of the relay cut-in time.
600 s]
Select 1 of 2 internal mechanical relays in
an array function. See
parameter 5-40 Function Relay for details.
On Delay
P 5-41
On Delay
P 5-41
Function:
[0.01 -
Enter the delay of the relay cutout time. Select
600 s]
1 of 2 internal mechanical relays in an array
function. See parameter 5-40 Function Relay for
details. If the selected event condition changes
before a delay timer expires, the relay output
is unaffected.
On Delay
O Delay
P 5-41
P 5-42
3
O Delay
P 5-42
105
3