Parameter Descriptions
13-91 Alert Action
Array [10]
Select the action that the frequency converter performs when
the event defined in parameter 13-90 Alert Trigger occurs.
Option:
[3]
Freeze output & warn
[4]
Stop
[5]
Stop & warning
[6]
Jogging
[7]
Jogging & warning
[8]
Max speed
[9]
Max speed & warn
[10]
Stop and trip
[11]
Stop and trip w manual
reset
[12]
Trip
[13]
Trip w manual reset
[14]
Trip Lock
13-92 Alert Text
Range:
Function:
Size
[0 -
Array [10]
related
20 ]
Enter the text that the frequency
*
converter shows in the display when the
event defined in parameter 13-90 Alert
Trigger occurs.
13-97 Alert Alarm Word
Range:
Function:
0
[0 - 4294967295 ] Shows the alarm word of a user-defined
*
alarm in hex code.
13-98 Alert Warning Word
Range:
Function:
0
[0 - 4294967295 ] Shows the warning word of a user-
*
defined alarm in hex code.
13-99 Alert Status Word
Range:
Function:
0
[0 - 4294967295 ] Shows the status word of a user-defined
*
alarm in hex code.