Parameter Descriptions
5-40 Function Relay
Option:
Function:
prepare switching the frequency
converter in open loop in an
emergency case.
[39]
Tracking error
When the difference between
calculated speed and actual speed in
parameter 4-35 Tracking Error is larger
than selected, the digital output/relay
is active.
[40]
Out of ref range
Active when the actual speed is
outside settings in
parameter 4-52 Warning Speed Low to
parameter 4-55 Warning Reference High.
[41]
Below reference,
Active when actual speed is below
low
speed reference setting.
[42]
Above ref, high
Active when actual speed is above
speed reference setting.
[43]
Extended PID
Limit
[45]
Bus ctrl.
Controls digital output/relay via bus.
The state of the output is set in
parameter 5-90 Digital & Relay Bus
Control. The output state is retained in
the event of bus timeout.
[46]
Bus ctrl, 1 if
Controls output via bus. The state of
timeout
the output is set in
parameter 5-90 Digital & Relay Bus
Control. If a bus timeout occurs, the
output state is set high (on).
[47]
Bus ctrl, 0 if
Controls output via bus. The state of
timeout
the output is set in
parameter 5-90 Digital & Relay Bus
Control. If a bus timeout occurs, the
output state is set low (Off).
[50]
On Reference
[51]
MCO controlled
[59]
Remote, enable,
no TW
[60]
Comparator 0
See parameter group 13-1*
Comparators. If comparator 0 in SLC is
true, the output goes high. Otherwise,
it is low.
[61]
Comparator 1
See parameter group 13-1*
Comparators. If comparator 1 in SLC is
true, the output goes high. Otherwise,
it is low.
[62]
Comparator 2
See parameter group 13-1*
Comparators. If comparator 2 in SLC is
true, the output goes high. Otherwise,
it is low.
[63]
Comparator 3
See parameter group 13-1*
Comparators. If comparator 3 in SLC is
true, the output goes high. Otherwise,
it is low.
MG33MO02
Programming Guide
5-40 Function Relay
Option:
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output
A
[81]
SL digital output
B
[82]
SL digital output
C
[83]
SL digital output
D
[84]
SL digital output
E
[85]
SL digital output
F
Danfoss A/S © 01/2018 All rights reserved.
Function:
See parameter group 13-1*
Comparators. If comparator 4 in SLC is
true, the output goes high. Otherwise,
it is low.
See parameter group 13-1* Smart Logic
Control. If comparator 5 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 0 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 1 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 2 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 3 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 4 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter group 13-4* Smart Logic
Control. If logic rule 5 in SLC is true,
the output goes high. Otherwise, it is
low.
See parameter 13-52 SL Controller
Action. Output A is low on smart logic
action [32]. Output A is high on smart
logic action [38].
See parameter 13-52 SL Controller
Action. Output B is low on smart logic
action [33]. Output B is high on smart
logic action [39].
See parameter 13-52 SL Controller
Action. Output C is low on smart logic
action [34]. Output C is high on smart
logic action [40].
See parameter 13-52 SL Controller
Action. Output D is low on smart logic
action [35]. Output D is high on smart
logic action [41].
See parameter 13-52 SL Controller
Action. Output E is low on smart logic
action [36]. Output E is high on smart
logic action [42].
See parameter 13-52 SL Controller
Action. Output F is low on smart logic
3
3
103