Parameter Descriptions
A
B
3
3
A
B
Illustration 3.42 Encoder Rotation Direction
5-70 Term 32/33 Pulses per Revolution
Range:
1024 N/A
[1 - 4096 N/A] Set the encoder pulses per
*
5-71 Term 32/33 Encoder Direction
Option:
[0]
Clockwise
*
[1]
Counter
clockwise
5-72 Term 32/33 Encoder Type
Option:
[0]
Quadrature A/B
*
Format
[1]
Single Channel
33
110
®
VLT
CW
CCW
Function:
revolution on the motor shaft. Read
the correct value from the encoder.
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to the
encoder.
Sets channel A 90° (electrical degrees)
behind channel B upon clockwise rotation of
the encoder shaft.
Sets channel A 90° (electrical degrees) ahead
of channel B upon clockwise rotation of the
encoder shaft.
Function:
NOTICE
This parameter is only available
with software version 48.XX.
Select the signal type of the encoder
connected to terminals 32, 33.
Encoder with 2 tracks: A and B, displaced
90° for detecting the rotational direction.
Encoder with 1 track connected to
terminal 33.
Danfoss A/S © 01/2018 All rights reserved.
AutomationDrive FC 301/302
5-72 Term 32/33 Encoder Type
Option:
[2]
Signle Channel
w/Dir.
3.6.8 5-8* I/O Options
5-80 AHF Cap Reconnect Delay
Range:
25 s
[1 - 120
*
s]
3.6.9 5-9* Bus-controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
0 N/A
[0 - 2147483647
*
N/A]
Bit 0
Digital output terminal 27
Bit 1
Digital output terminal 29
Bit 2
Digital output terminal X 30/6
Bit 3
Digital output terminal X 30/7
Bit 4
Relay 1 output terminal
Bit 5
Relay 2 output terminal
Bit 6
Option B relay 1 output terminal
Bit 7
Option B relay 2 output terminal
Bit 8
Option B relay 3 output terminal
Bit 9–15
Reserved for future terminals
Bit 16
Option C relay 1 output terminal
Bit 17
Option C relay 2 output terminal
Bit 18
Option C relay 3 output terminal
Bit 19
Option C relay 4 output terminal
Bit 20
Option C relay 5 output terminal
Bit 21
Option C relay 6 output terminal
Bit 22
Option C relay 7 output terminal
Bit 23
Option C relay 8 output terminal
Bit 24–31
Reserved for future terminals
Table 3.22 Bus-controlled Digital Outputs and Relays
Function:
Encoder with 1 track connected to
terminal 33. The direction is set with a
signal on terminal 32: 0 V = forward/
clockwise, 24 V = reverse/counter
clockwise.
Function:
Guarantees a minimum off-time for the
capacitors. The timer starts once the AHF
capacitor disconnects and has to expire before
the output is allowed to be on again. It only
turns on again if the frequency converter
power is 20–30%.
Function:
This parameter holds the state of the
digital outputs and relays that is
controlled by bus.
A logical 1 indicates that the output
is high or active.
A logical 0 indicates that the output
is low or inactive.
MG33MO02